startTime=0 stopTime=86400 tolerance=1e-06 numberOfIntervals=2500 stepSize=34.56 wasm FMU (me: FMI 3.0 Model Exchange, integrated by omc with the model's own solver (DASKR unless its annotation says otherwise; IDA over the fmi-ls-dae residuals for a --daeMode model)): simulate(Buildings.Fluid.DXSystems.Cooling.AirSource.Validation.SingleSpeed,startTime=0,stopTime=86400,tolerance=1e-06,numberOfIntervals=2500,outputFormat="empty",variableFilter="",fileNamePrefix="Buildings_13_Buildings.Fluid.DXSystems.Cooling.AirSource.Validation.SingleSpeed",simflags="-abortSlowSimulation -alarm=240 -lv LOG_STATS -startTime=0 -stopTime=86400 -tolerance=1e-06 -stepSize=34.56 -noemit -s fmi3:me",resimulateExecutable="../Buildings_13_Buildings_Fluid_DXSystems_Cooling_AirSource_Validation_SingleSpeed.fmu") LOG_STDOUT | info | wasm artifact loaded in 0.1 ms (model kernel linked against the cached adapter, 0.7 MB) Buildings.Fluid.DXSystems.Cooling.AirSource.Validation.SingleSpeed: logStatusWarning: /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 13.0.2-maint.13.x/Fluid/DXSystems/Cooling/BaseClasses/PartialCapacity.mo:121: *** Warning: Evaporator temperature TEvaIn is out of bounds in DX coil model at time = 25200. stage = 1 TEvaInMin = 285.928 Kelvin (12.7778 degC) TEvaIn = 298.441 Kelvin (25.2914 degC) TEvaInMax = 297.039 Kelvin (23.8889 degC) Extrapolation can introduce large errors. This warning will only be reported once for each stage. LOG_STDOUT | info | ModelExchange instantiated in 218.8 ms LOG_STDOUT | info | ModelExchange run: 1380 steps, 9498 evaluations, 985 Jacobians, 0 state events, 24 time events, 2549 samples in 57.9 ms LOG_SUCCESS | info | The simulation finished successfully.