(cd run_OMSimulator-cs-euler && /home/hudson/saved_omc/OMSimulator/install/bin/OMSimulator --stripRoot --tempDir=temp_BuildingSystems_BuildingSystems_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator_OMSimulator-cs-euler_fmu --startTime=0 --stopTime=86400 --stepSize=34.56 --mode=cs --timeout=240 --tolerance=1e-08 ../BuildingSystems_BuildingSystems_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator_OMSimulator-cs-euler.fmu) info: *** FMU Simulation Info *** - model : BuildingSystems.Fluid.HeatPumps.ModularReversible.Examples.Modular_OneRoomRadiator (co-simulation) - fmiVersion: 2.0 - startTime : 0.000000 - stopTime : 86400.000000 - tolerance : 1e-08 - stepSize : 34.56 LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems master/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:389:3-396:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((pumHeaPumSou.nominalValuesDefineDefaultPressureCurve)) --> "*** Warning in Modular_OneRoomRadiator.pumHeaPumSou: Mover is flow or pressure controlled and uses default pressure curve. | | | | This leads to an approximate power consumption. | | | | Set nominalValuesDefineDefaultPressureCurve=true to suppress this warning." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems master/Fluid/HeatPumps/ModularReversible/RefrigerantCycle/BaseClasses/PartialTableData2D.mo:144:3-149:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((heaPum.refCyc.refCycHeaPumCoo.mCon_flow_nominal <= heaPum.refCyc.refCycHeaPumCoo.mCon_flow_max)) --> "In Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo: The nominal condenser mass flow rate (0.956023 kg/s) is bigger than the | | | | maximal value (0.841737 kg/s) for the table data | | | | when assuming a temperature spread between 3 and 10 K, as in EN 14511." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems master/Fluid/HeatPumps/ModularReversible/RefrigerantCycle/BaseClasses/PartialTableData2D.mo:156:3-161:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((heaPum.refCyc.refCycHeaPumCoo.mEva_flow_nominal <= heaPum.refCyc.refCycHeaPumCoo.mEva_flow_max)) --> "In Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo: The nominal evaporator mass flow rate (5.58642 kg/s) is bigger than the | | | | maximal value (3.03188 kg/s) for the table data | | | | when assuming a temperature spread between 3 and 10 K, as in EN 14511." info: Result file: BuildingSystems_BuildingSystems_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator_OMSimulator-cs-euler_res.mat (bufferSize=10) info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.datTab.devIde will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.devIde will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabPEle.delimiter will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabPEle.fileName will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabPEle.tableName will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabQUse_flow.delimiter will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabQUse_flow.fileName will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabQUse_flow.tableName will not be stored in the result file, because the signal type is not supported info: Variable Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumHea.devIde will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapCoo.tabBou.delimiter will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapCoo.tabBou.fileName will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapCoo.tabBou.tableName will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapHea.tabBou.delimiter will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapHea.tabBou.fileName will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapHea.tabBou.tableName will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.timTab.delimiter will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.timTab.fileName will not be stored in the result file, because the signal type is not supported info: Parameter Modular_OneRoomRadiator.timTab.tableName will not be stored in the result file, because the signal type is not supported LOG_ASSERT | error | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems master/Media/Water.mo:65:5-66:128:writable] | | | | The following assertion has been violated at time 103.680000 | | | | ((noEvent(heaPum.con.vol.dynBal.medium.T <= 403.15))) --> "In Modular_OneRoomRadiator.heaPum.con.vol.dynBal.medium: Temperature T = 485.063 K exceeded its maximum allowed value of 130 degC (403.15 Kelvin) as required from medium model "BuildingSystems.Media.Water"." error: [fmi2logger] [fmi2Error] Modular_OneRoomRadiator/logFmi2Call: internalEventUpdate: terminated by an assertion. error: [stepUntil] fmi2_doStep failed for FMU "Modular_OneRoomRadiator.root.Modular_OneRoomRadiator" LOG_ASSERT | error | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems master/Media/Water.mo:65:5-66:128:writable] | | | | The following assertion has been violated at time 103.680000 | | | | ((noEvent(heaPum.con.vol.dynBal.medium.T <= 403.15))) --> "In Modular_OneRoomRadiator.heaPum.con.vol.dynBal.medium: Temperature T = 485.063 K exceeded its maximum allowed value of 130 degC (403.15 Kelvin) as required from medium model "BuildingSystems.Media.Water"." error: [fmi2logger] [fmi2Error] Modular_OneRoomRadiator/logFmi2Call: fmi2GetBoolean: terminated by an assertion. error: [updateSignals] failed to fetch variable oneRooRadHeaPumCtr.swiSecForCoo.u2 Traceback (most recent call last): File "", line 198, in _run_module_as_main File "", line 88, in _run_code File "/home/hudson/saved_omc/OMSimulator/install/lib/x86_64-linux-gnu/OMSimulator/__main__.py", line 38, in sys.exit(main()) ~~~~^^ File "/home/hudson/saved_omc/OMSimulator/install/lib/x86_64-linux-gnu/OMSimulator/cli.py", line 309, in main handler(args.model, args) ~~~~~~~^^^^^^^^^^^^^^^^^^ File "/home/hudson/saved_omc/OMSimulator/install/lib/x86_64-linux-gnu/OMSimulator/cli.py", line 176, in _runFMU fmu.simulate() ~~~~~~~~~~~~^^ File "/home/hudson/saved_omc/OMSimulator/install/lib/x86_64-linux-gnu/OMSimulator/fmu.py", line 906, in simulate raise RuntimeError(f"Failed to simulate model: {status}") RuntimeError: Failed to simulate model: Status.error info: 0 warnings info: 4 errors