Environment - simulationEnvironment:
startTime=0
stopTime=1
tolerance=1e-06
numberOfIntervals=50
stepSize=0.02
Regular simulation: ./PowerGrids_dev_PowerGrids.Electrical.Test.TwoBusesResistiveTransmissionLineFault  -abortSlowSimulation -alarm=480  -emit_protected -lv LOG_STATS
LOG_STDOUT        | info    | Using sparse solver for linear system 0,
|                 | |       | because density of 0.062 remains under threshold of 0.200.
LOG_STDOUT        | info    | Using sparse solver for linear system 1,
|                 | |       | because density of 0.094 remains under threshold of 0.200.
LOG_STDOUT        | info    | The maximum density for using sparse solvers can be specified
|                 | |       | using the runtime flag '<-lssMaxDensity=value>'.
LOG_STDOUT        | warning | Internal Numerical Jacobians without coloring are currently not supported by IDA with KLU. Colored numerical Jacobian will be used.
LOG_SUCCESS       | info    | The initialization finished successfully without homotopy method.
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/PowerGrids 2.0.0-develop/Electrical/BaseClasses/SolutionChecking.mo:35:5-35:162:writable]
|                 | |       | The following assertion has been violated at time 0.400000
|                 | |       | ((infiniteBusA.IPuCheck < infiniteBusA.IPuMax)) --> "Current too high (IPu=5.41126 > 2.5), check if the numerical solution is valid"
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/PowerGrids 2.0.0-develop/Electrical/BaseClasses/SolutionChecking.mo:34:5-34:161:writable]
|                 | |       | The following assertion has been violated at time 0.400000
|                 | |       | ((transmissionLine.threePhaseFault.VPuCheck > transmissionLine.threePhaseFault.VPuMin)) --> "Voltage too low (VPu=0.469697 < 0.7), check if the numerical solution is valid"
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/PowerGrids 2.0.0-develop/Electrical/BaseClasses/SolutionChecking.mo:35:5-35:162:writable]
|                 | |       | The following assertion has been violated at time 0.400000
|                 | |       | ((transmissionLine.threePhaseFault.IPuCheck < transmissionLine.threePhaseFault.IPuMax)) --> "Current too high (IPu=15.6566 > 2.5), check if the numerical solution is valid"
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/PowerGrids 2.0.0-develop/Electrical/BaseClasses/SolutionChecking.mo:34:5-34:161:writable]
|                 | |       | The following assertion has been violated at time 0.400000
|                 | |       | ((transmissionLine.busFault.VPuCheck > transmissionLine.busFault.VPuMin)) --> "Voltage too low (VPu=0.469697 < 0.7), check if the numerical solution is valid"
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/PowerGrids 2.0.0-develop/Electrical/BaseClasses/SolutionChecking.mo:35:5-35:162:writable]
|                 | |       | The following assertion has been violated at time 0.400000
|                 | |       | ((infiniteBusB.IPuCheck < infiniteBusB.IPuMax)) --> "Current too high (IPu=9.22078 > 2.5), check if the numerical solution is valid"
LOG_STATS         | info    | ### STATISTICS ###
|                 | |       | | timer
|                 | |       | | |    0.0212849s          reading init.xml
|                 | |       | | |   0.00189644s          reading info.xml
|                 | |       | | |   0.00641536s [ 73.5%] pre-initialization
|                 | |       | | |  0.000502973s [  5.8%] initialization
|                 | |       | | |    5.199e-06s [  0.1%] steps
|                 | |       | | |   0.00158098s [ 18.1%] solver (excl. callbacks)
|                 | |       | | |  0.000349675s [  4.0%] creating output-file
|                 | |       | | |  0.000427254s [  4.9%] event-handling
|                 | |       | | |  0.000113846s [  1.3%] overhead
|                 | |       | | | -0.000670759s [ -7.7%] simulation
|                 | |       | | |   0.00872453s [100.0%] total
|                 | |       | | events
|                 | |       | | |     2 state events
|                 | |       | | |     0 time events
|                 | |       | | solver: ida
|                 | |       | | |    47 steps taken
|                 | |       | | |    47 calls of functionODE
|                 | |       | | |    41 evaluations of jacobian
|                 | |       | | |     0 error test failures
|                 | |       | | |     0 convergence test failures
|                 | |       | | | 0.000518557s time of jacobian evaluation
LOG_SUCCESS       | info    | The simulation finished successfully.