Environment - simulationEnvironment:
startTime=0
stopTime=86400
tolerance=1e-06
numberOfIntervals=2500
stepSize=34.56
Regular simulation: ./Buildings_11_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanCVF.Validation.Controller  -abortSlowSimulation -alarm=400  -emit_protected -lv LOG_STATS
LOG_ASSERT        | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated during initialization at time 0.000000
|                 | |       | ((parFanCon.ala.not11.y)) --> "Warning: fan has been commanded OFF but still ON."
LOG_ASSERT        | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated during initialization at time 0.000000
|                 | |       | ((not parFanCon.ala.truDel3.y)) --> "Warning: the damper is leaking."
LOG_SUCCESS       | info    | The initialization finished successfully without homotopy method.
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated at time 6225.000001
|                 | |       | ((not parFanCon.ala.truDel2.y)) --> "Warning: airflow sensor should be calibrated."
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated at time 17100.000003
|                 | |       | ((parFanCon.ala.not2.y)) --> "Warning: airflow is less than 70% of the setpoint."
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated at time 20015.482861
|                 | |       | ((parFanCon.ala.not1.y)) --> "Warning: airflow is less than 50% of the setpoint."
LOG_ASSERT        | info    | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.1-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable]
|                 | |       | The following assertion has been violated at time 45900.000005
|                 | |       | ((not parFanCon.ala.truDel6.y)) --> "Warning: the valve is leaking."
LOG_STATS         | info    | ### STATISTICS ###
|                 | |       | | timer
|                 | |       | | |    0.0278339s          reading init.xml
|                 | |       | | |   0.00190124s          reading info.xml
|                 | |       | | |   0.00137107s [  1.3%] pre-initialization
|                 | |       | | |  0.000332905s [  0.3%] initialization
|                 | |       | | |   1.5038e-05s [  0.0%] steps
|                 | |       | | |    0.0159158s [ 15.4%] solver (excl. callbacks)
|                 | |       | | |   0.00633111s [  6.1%] creating output-file
|                 | |       | | |    0.0313692s [ 30.4%] event-handling
|                 | |       | | |   0.00070559s [  0.7%] overhead
|                 | |       | | |    0.0472906s [ 45.8%] simulation
|                 | |       | | |     0.103331s [100.0%] total
|                 | |       | | events
|                 | |       | | |    93 state events
|                 | |       | | |   772 time events
|                 | |       | | solver: dassl
|                 | |       | | | 12315 steps taken
|                 | |       | | | 14438 calls of functionODE
|                 | |       | | | 10353 evaluations of jacobian
|                 | |       | | |    75 error test failures
|                 | |       | | |     0 convergence test failures
|                 | |       | | | 0.0221308s time of jacobian evaluation
LOG_SUCCESS       | info    | The simulation finished successfully.