Environment - simulationEnvironment: startTime=0 stopTime=14400 tolerance=1e-06 numberOfIntervals=2500 stepSize=5.76 Regular simulation: ./Buildings_latest_Buildings.Fluid.Chillers.ModularReversible.Validation.TableData2DLoadDep_HeatRecovery -abortSlowSimulation -alarm=800 -emit_protected -lv LOG_STATS LOG_STDOUT | info | ... loading "tab" from "/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings master/Resources/Data/Fluid/Chillers/ModularReversible/Validation/ElectricEIR_HeatRecovery.mos" LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings master/Fluid/Chillers/ModularReversible/TableData2DLoadDep.mo:57:3-59:51:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((chi.QCoo_flow_nominal <= 0.0)) --> "Variable violating max constraint: chi.QCoo_flow_nominal <= 0.0, has value: 1" LOG_ASSERT | error | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Modelica 4.1.0+maint.om/Blocks/Logical.mo:523:5-523:67:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((chi.eff.hys.uHigh > chi.eff.hys.uLow)) --> "Hysteresis limits wrong (uHigh <= uLow)" LOG_ASSERT | info | simulation terminated by an assertion at initialization