/home/hudson/saved_omc/OMSimulator/install/bin/OMSimulator -r=Buildings_9_Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Validation.Controller_res.mat --tempDir=temp_Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller_fmu --startTime=0 --stopTime=86400 --timeout=50 --tolerance=1e-06 Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.fmu LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/ASHRAE/G36/AHUs/SingleZone/VAV/Controller.mo:667:3-673:57:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((conVAV.ySupFan >= max(0.0, max(0.0, max(conVAV.conEco.supFanSpe_min, 0.0))) and conVAV.ySupFan <= min(1.0, min(1.0, min(conVAV.conEco.supFanSpe_max, 1.0))))) --> "Variable violating min/max constraint: max(0.0, max(0.0, max(conVAV.conEco.supFanSpe_min, 0.0))) <= conVAV.ySupFan <= min(1.0, min(1.0, min(conVAV.conEco.supFanSpe_max, 1.0))), has value: 0" LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/ASHRAE/G36/VentilationZones/ASHRAE62_1/Setpoints.mo:119:3-123:59:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((conVAV.outAirSetPoi.VMinOA_flow >= 0.006 and conVAV.outAirSetPoi.VMinOA_flow <= 0.25)) --> "Variable violating min/max constraint: 0.006 <= conVAV.outAirSetPoi.VMinOA_flow <= 0.25, has value: 0" info: maximum step size for 'model.root': 0.001000 info: Result file: Buildings_9_Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Validation.Controller_res.mat (bufferSize=1) info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.assMes.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.assMes1.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.assMes2.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.conEco.ecoHigLim.assMes.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.conEco.ecoHigLim.assMes2.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.frePro.disMinVenWar.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_AHUs_SingleZone_VAV_Validation_Controller.conVAV.frePro.shuDowWar.message will not be stored in the result file, because the signal type is not supported error: [operator()] Timeout occurred during simulation info: 0 warnings info: 1 errors info: Final Statistics for 'model.root': NumSteps = 239276 NumRhsEvals = 239281 NumLinSolvSetups = 11970 NumNonlinSolvIters = 239280 NumNonlinSolvConvFails = 0 NumErrTestFails = 1 [CVODE ERROR] CVode cvode_mem = NULL illegal. error: [doStep] SUNDIALS_ERROR: CVode() failed with flag = -21