/home/hudson/saved_omc/OMSimulator/install/bin/OMSimulator -r=Buildings_11_Buildings.Fluid.HeatPumps.ModularReversible.Examples.Modular_OneRoomRadiator_res.mat --tempDir=temp_Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator_fmu --startTime=0 --stopTime=86400 --timeout=400 --tolerance=1e-08 Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.fmu LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:389:3-396:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((pumHeaPumSou.nominalValuesDefineDefaultPressureCurve)) --> "*** Warning in Modular_OneRoomRadiator.pumHeaPumSou: Mover is flow or pressure controlled and uses default pressure curve. | | | | This leads to an approximate power consumption. | | | | Set nominalValuesDefineDefaultPressureCurve=true to suppress this warning." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Fluid/HeatPumps/ModularReversible/RefrigerantCycle/BaseClasses/PartialTableData2D.mo:144:3-149:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((heaPum.refCyc.refCycHeaPumCoo.mCon_flow_nominal <= heaPum.refCyc.refCycHeaPumCoo.mCon_flow_max)) --> "In Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo: The nominal condenser mass flow rate (0.956023 kg/s) is bigger than the | | | | maximal value (0.841737 kg/s) for the table data | | | | when assuming a temperature spread between 3 and 10 K, as in EN 14511." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Fluid/HeatPumps/ModularReversible/RefrigerantCycle/BaseClasses/PartialTableData2D.mo:156:3-161:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((heaPum.refCyc.refCycHeaPumCoo.mEva_flow_nominal <= heaPum.refCyc.refCycHeaPumCoo.mEva_flow_max)) --> "In Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo: The nominal evaporator mass flow rate (5.58642 kg/s) is bigger than the | | | | maximal value (3.03188 kg/s) for the table data | | | | when assuming a temperature spread between 3 and 10 K, as in EN 14511." info: maximum step size for 'model.root': 0.001000 info: Result file: Buildings_11_Buildings.Fluid.HeatPumps.ModularReversible.Examples.Modular_OneRoomRadiator_res.mat (bufferSize=1) info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.datTab.devIde will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.devIde will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabPEle.fileName will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabPEle.tableName will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabQUse_flow.fileName will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo.tabQUse_flow.tableName will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumHea.devIde will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapCoo.tabBou.fileName will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapCoo.tabBou.tableName will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapHea.tabBou.fileName will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.heaPum.safCtr.opeEnv.bouMapHea.tabBou.tableName will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.timTab.fileName will not be stored in the result file, because the signal type is not supported info: Parameter model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator.timTab.tableName will not be stored in the result file, because the signal type is not supported error: [operator()] Timeout occurred during simulation info: 0 warnings info: 1 errors error: [fmi2logger] /var/lib/jenkins1/ws/OpenModelicaLibraryTestingWork/OpenModelicaLibraryTesting/Buildings_11_Buildings.Fluid.HeatPumps.ModularReversible.Examples.Modular_OneRoomRadiator/temp_Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator_fmu/model-o7365jsb/temp/0001_Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator (logStatusError): fmi2SetTime: Illegal model exchange call sequence. fmi2SetTime is not allowed in model_state_terminated state. error: [updateInputs] fmi2_setTime failed for FMU "model.root.Buildings_11_Buildings_Fluid_HeatPumps_ModularReversible_Examples_Modular_OneRoomRadiator"