python3 -m fmpy simulate --output-file Buildings_10_Buildings.Examples.ScalableBenchmarks.BuildingVAV.Examples.OneFloor_OneZone_res.csv --start-time 0 --stop-time 604800 --timeout 50 --relative-tolerance 1e-06 --interface-type ModelExchange --solver CVode --output-interval 241.92 Buildings_10_Buildings_Examples_ScalableBenchmarks_BuildingVAV_Examples_OneFloor_OneZone.fmu LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:417:3-427:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((not (fan[1].per.etaHydMet == Buildings.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.Power_VolumeFlowRate or fan[1].per.etaHydMet == Buildings.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.EulerNumber))) --> "*** Warning in OneFloor_OneZone.fan: Mover has per.etaHydMet=.Power_VolumeFlowRate or per.etaHydMet=.EulerNumber. | | | | This requires per.pressure to be provided. | | | | Because it is not, the model overrides this setting by using per.etaHydMet=.NotProvided. | | | | Also consider using models under Movers.Preconfigured which autopopulate a pressure curve." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:429:3-439:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((fan[1].per.haveWMot_nominal or not (fan[1].per.etaMotMet == Buildings.Fluid.Movers.BaseClasses.Types.MotorEfficiencyMethod.Efficiency_MotorPartLoadRatio or fan[1].per.etaMotMet == Buildings.Fluid.Movers.BaseClasses.Types.MotorEfficiencyMethod.GenericCurve))) --> "*** Warning in OneFloor_OneZone.fan: Mover has per.etaMotMet=.Efficiency_MotorPartLoadRatio or per.etaMotMet=.GenericCurve. | | | | This requires per.WMot_nominal or per.pressure to be provided. Because neither is provided, | | | | the model overrides this setting and by using per.etaMotMet=.NotProvided. | | | | Also consider using models under Movers.Preconfigured which autopopulate a pressure curve." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Fluid/HeatExchangers/WetCoilEffectivenessNTU.mo:71:3-76:35:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((cooCoi[1].SHR >= 0.0 and cooCoi[1].SHR <= 1.0)) --> "Variable violating min/max constraint: 0.0 <= cooCoi[1].SHR <= 1.0, has value: -1.04344e-25" LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:99:3-99:89:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((fanRet[1].etaHyd >= 0.0)) --> "Variable violating min constraint: 0.0 <= fanRet[1].etaHyd, has value: -1.22764e-22" LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Fluid/Movers/BaseClasses/PowerInterface.mo:46:3-47:27:writable] | | | | The following assertion has been violated at time 0.000000 | | | | ((fanRet[1].heaDis.etaHyd >= 0.0)) --> "Variable violating min constraint: 0.0 <= fanRet[1].heaDis.etaHyd, has value: -1.14341e-19"