startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_latest_Buildings.Controls.OBC.ASHRAE.G36.ThermalZones.Validation.Alarms -abortSlowSimulation -alarm=480 -emit_protected -lv LOG_STATS stdout | info | The initialization finished successfully without homotopy method. assert | warning | The following assertion has been violated at time 1601.347898 | | | | not zonAla.tenMinDur4.y assert | warning | Warning: the zone CO2 concentration exceeds setpoint plus 10%.0 assert | warning | The following assertion has been violated at time 3759.513744 | | | | not zonAla.levThrLow.y assert | warning | Warning: zone temperature is 2 degC lower than the heating setpoint assert | warning | The following assertion has been violated at time 3910.449757 | | | | not zonAla.levTwoLow.y assert | warning | Warning: zone temperature is 3 degC lower than the heating setpoint assert | warning | The following assertion has been violated at time 4337.397953 | | | | not zonAla.and6.y assert | warning | Warning: the zone CO2 concentration exceeds 600 ppm in unoccupied mode. The CO2 sensor may be out of calibration. LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.00300282s reading init.xml | | | | | | 0.000237345s reading info.xml | | | | | | 0.00019216s pre-initialization | | | | | | 5.3591e-05s [ 0.9%] initialization | | | | | | 2.956e-06s [ 0.1%] steps | | | | | | 0.00114929s [ 20.0%] creating output-file | | | | | | 0.000665919s [ 11.6%] event-handling | | | | | | 0.000488813s [ 8.5%] overhead | | | | | | 0.00320458s [ 55.7%] simulation | | | | | | 0.0057573s [100.0%] total | | | | | events | | | | | | 14 state events | | | | | | 3 time events | | | | | solver: euler | | | | | | 38286 steps taken | | | | | | 38286 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation stdout | info | The simulation finished successfully.