Regular simulation: ./Buildings_master_Buildings.Examples.ChillerPlant.DataCenterContinuousTimeControl -abortSlowSimulation -alarm=480 -lv LOG_STATS stdout | info | ... loading "tab1" from "/var/lib/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.0.0-master/Resources/weatherdata/USA_CA_San.Francisco.Intl.AP.724940_TMY3.mos" assert | warning | The following assertion has been violated during initialization at time 13046400.000000 | | | | fan.nominalValuesDefineDefaultPressureCurve assert | warning | *** Warning: You are using a flow or pressure controlled mover with the | | | | default pressure curve. | | | | This leads to approximate calculations of the electrical power | | | | consumption. Add the correct pressure curve in the record per | | | | to obtain an accurate computation. | | | | Setting nominalValuesDefineDefaultPressureCurve=true will suppress this warning. assert | warning | The following assertion has been violated during initialization at time 13046400.000000 | | | | pumCHW.nominalValuesDefineDefaultPressureCurve assert | warning | *** Warning: You are using a flow or pressure controlled mover with the | | | | default pressure curve. | | | | This leads to approximate calculations of the electrical power | | | | consumption. Add the correct pressure curve in the record per | | | | to obtain an accurate computation. | | | | Setting nominalValuesDefineDefaultPressureCurve=true will suppress this warning. assert | warning | The following assertion has been violated during initialization at time 13046400.000000 | | | | pumCW.nominalValuesDefineDefaultPressureCurve assert | warning | *** Warning: You are using a flow or pressure controlled mover with the | | | | default pressure curve. | | | | This leads to approximate calculations of the electrical power | | | | consumption. Add the correct pressure curve in the record per | | | | to obtain an accurate computation. | | | | Setting nominalValuesDefineDefaultPressureCurve=true will suppress this warning. assert | warning | The following assertion has been violated during initialization at time 13046400.000000 | | | | noEvent(cooTow.vol.dynBal.medium.T >= 272.15) assert | error | In Buildings.Examples.ChillerPlant.DataCenterContinuousTimeControl.cooTow.vol.dynBal.medium: Temperature T = -2.06075e+20 K exceeded its minimum allowed value of -1 degC (272.15 Kelvin) as required from medium model "Buildings.Media.Water". assert | info | simulation terminated by an assertion at initialization