OMSimulator --tempDir=temp_Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse_fmu --startTime=0 --stopTime=7200 --timeout=50 --tolerance=1e-06 Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse.fmu warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:59: The following assertion has been violated at time 0.000000 false assert | warning | Nominal variable violating min constraint: 0.0 <= evaSho.m, has value: -3.10146 warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:59: The following assertion has been violated at time 0.000000 false assert | warning | Nominal variable violating min constraint: 0.0 <= evaNor.m, has value: -3.10146 warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:187: The following assertion has been violated during initialization at time 0.000000 evaSho.nomVal.gamma <= evaSho.gammaMax assert | warning | *** Warning: In DX coil model, gamma is too large for these coil conditions. | | | | Instead of gamma = 1.5, a value of 1.00359, which | | | | corresponds to a mass transfer effectiveness of 0.8, will be used. | | | | Coil nominal performance data are: | | | | nomVal.m_flow_nominal = 0.497018 | | | | dX_nominal = XEvaOut_nominal-XEvaWetBulOut_nominal = 0.00614376 - 0.00715296 = -0.0010092 | | | | QLat_flow_nominal = -1000 warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:173: The following assertion has been violated during initialization at time 0.000000 evaSho.dX_nominal > 1e-10 assert | warning | *** Warning: In DX coil model, dX_nominal = -0.0010092 | | | | This means that the coil is not dehumidifying air at the nominal conditions. | | | | Check nominal parameters. | | | | Nominal values: | | | | Q_flow_nominal = -5000 | | | | COP_nominal = 3 | | | | m_flow_nominal = 0.497018 | | | | TEvaIn_nominal = 292.55 (= 19.4 degC) | | | | TConIn_nominal = 308.15 (= 35 degC) | | | | phiIn_nominal = 0.5 | | | | tWet = 1400 | | | | gamma = 1.5 | | | | p_nominal = 101325 warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:187: The following assertion has been violated during initialization at time 0.000000 evaNor.nomVal.gamma <= evaNor.gammaMax assert | warning | *** Warning: In DX coil model, gamma is too large for these coil conditions. | | | | Instead of gamma = 1.5, a value of 1.00359, which | | | | corresponds to a mass transfer effectiveness of 0.8, will be used. | | | | Coil nominal performance data are: | | | | nomVal.m_flow_nominal = 0.497018 | | | | dX_nominal = XEvaOut_nominal-XEvaWetBulOut_nominal = 0.00614376 - 0.00715296 = -0.0010092 | | | | QLat_flow_nominal = -1000 warning: Buildings_maint_7_0_x_Buildings_Fluid_HeatExchangers_DXCoils_BaseClasses_Examples_EvaporationPulse (logStatusWarning): /home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 7.0.3-maint.7.0.x/Fluid/HeatExchangers/DXCoils/BaseClasses/Evaporation.mo:173: The following assertion has been violated during initialization at time 0.000000 evaNor.dX_nominal > 1e-10 assert | warning | *** Warning: In DX coil model, dX_nominal = -0.0010092 | | | | This means that the coil is not dehumidifying air at the nominal conditions. | | | | Check nominal parameters. | | | | Nominal values: | | | | Q_flow_nominal = -5000 | | | | COP_nominal = 3 | | | | m_flow_nominal = 0.497018 | | | | TEvaIn_nominal = 292.55 (= 19.4 degC) | | | | TConIn_nominal = 308.15 (= 35 degC) | | | | phiIn_nominal = 0.5 | | | | tWet = 1400 | | | | gamma = 1.5 | | | | p_nominal = 101325 info: maximum step size for 'model.root': 0.001000 info: Result file: model_res.mat (bufferSize=10) error: [operator()] Timeout occurred during simulation info: 6 warnings info: 1 errors info: Final Statistics for 'model.root': NumSteps = 755077 NumRhsEvals = 755078 NumLinSolvSetups = 37755 NumNonlinSolvIters = 755077 NumNonlinSolvConvFails = 0 NumErrTestFails = 0 [CVODE ERROR] CVode cvode_mem = NULL illegal. error: [doStep] SUNDIALS_ERROR: CVode() failed with flag = -21