/home/hudson/saved_omc/OMSimulator/install/bin/OMSimulator -r=Buildings_9_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanVVF.Subsequences.Validation.Alarms_res.mat --tempDir=temp_Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms_fmu --startTime=0 --stopTime=7200 --timeout=50 --tolerance=1e-06 Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.fmu info: model doesn't contain any continuous state LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((ala.not7.y)) --> "Warning: discharge air temperature is 8 degC less than the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((ala.not10.y)) --> "Warning: fan has been commanded ON but still OFF." info: Result file: Buildings_9_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.ParallelFanVVF.Subsequences.Validation.Alarms_res.mat (bufferSize=1) info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes1.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes2.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes3.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes4.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes5.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes6.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes7.message will not be stored in the result file, because the signal type is not supported info: Variable model.root.Buildings_9_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_ParallelFanVVF_Subsequences_Validation_Alarms.ala.assMes8.message will not be stored in the result file, because the signal type is not supported LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 964.800000 | | | | ((ala.not2.y)) --> "Warning: airflow is less than 70% of the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2713.600000 | | | | ((ala.not1.y)) --> "Warning: airflow is less than 50% of the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 3750.000000 | | | | ((ala.not5.y)) --> "Warning: the damper is leaking." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 3778.800000 | | | | ((ala.not11.y)) --> "Warning: fan has been commanded OFF but still ON." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.3-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6229.800000 | | | | ((ala.not4.y)) --> "Warning: airflow sensor should be calibrated."