python3 -m fmpy simulate --output-file Buildings_11_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.Reheat.Subsequences.Validation.Alarms_res.csv --start-time 0 --stop-time 7200 --timeout 400 --relative-tolerance 1e-06 --interface-type ModelExchange --solver CVode --output-interval 2.88 Buildings_11_Buildings_Controls_OBC_ASHRAE_G36_TerminalUnits_Reheat_Subsequences_Validation_Alarms.fmu LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 850.000000 | | | | ((ala.not7.y)) --> "Warning: discharge air temperature is 8 degC less than the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 956.640000 | | | | ((ala.not2.y)) --> "Warning: airflow is less than 70% of the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2701.920000 | | | | ((ala.not1.y)) --> "Warning: airflow is less than 50% of the setpoint." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala.truDel3.y)) --> "Warning: the damper is leaking." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000000 | | | | ((not ala.truDel2.y)) --> "Warning: airflow sensor should be calibrated."