python3 -m fmpy simulate --output-file BuildingSystems_BuildingSystems.Applications.SolarThermalSystems.SolarThermalSystem1_res.csv --start-time 0 --stop-time 3.1536e+07 --timeout 50 --relative-tolerance 1e-06 --interface-type ModelExchange --solver CVode --output-interval 12614.4 BuildingSystems_BuildingSystems_Applications_SolarThermalSystems_SolarThermalSystem1.fmu LOG_STDOUT | info | ... loading "tab1" from "/tmp/tmpr2e5m5_k/resources/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems 2.0.0-master/Climate/weather/Egypt_ElGouna.txt" LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems 2.0.0-master/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:417:3-426:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((not (pump.per.etaHydMet == BuildingSystems.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.Power_VolumeFlowRate or pump.per.etaHydMet == BuildingSystems.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.EulerNumber))) --> "*** Warning in SolarThermalSystem1.pump: Mover has per.etaHydMet=.Power_VolumeFlowRate or per.etaHydMet=.EulerNumber. | | | | This requires per.pressure to be provided. | | | | Because it is not, the model overrides this setting by using per.etaHydMet=.NotProvided." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems 2.0.0-master/Fluid/Movers/BaseClasses/PartialFlowMachine.mo:428:3-437:39:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((pump.per.haveWMot_nominal or not (pump.per.etaMotMet == BuildingSystems.Fluid.Movers.BaseClasses.Types.MotorEfficiencyMethod.Efficiency_MotorPartLoadRatio or pump.per.etaMotMet == BuildingSystems.Fluid.Movers.BaseClasses.Types.MotorEfficiencyMethod.GenericCurve))) --> "*** Warning in SolarThermalSystem1.pump: Mover has per.etaMotMet=.Efficiency_MotorPartLoadRatio or per.etaMotMet=.GenericCurve. | | | | This requires per.WMot_nominal or per.pressure to be provided. Because neither is provided, | | | | the model overrides this setting and by using per.etaMotMet=.NotProvided." LOG_ASSERT | error | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/BuildingSystems 2.0.0-master/Fluid/Movers/FlowControlled_m_flow.mo:93:3-98:58:writable] | | | | The following assertion has been violated at time 26683.059070 | | | | (((-pump.dp) <= 4e4)) --> "In SolarThermalSystem1.pump: Model operates with head -dp = 56398.5 Pa, | | | | exceeding the pressure allowed by the parameter SolarThermalSystem1.pump.dpMax. | | | | This can happen if the model forces a high mass flow rate through a closed actuator, | | | | or if the performance record is unreasonable. Please verify your model, and | | | | consider using one of the other pump or fan models." Traceback (most recent call last): File "/usr/lib/python3.10/runpy.py", line 196, in _run_module_as_main return _run_code(code, main_globals, None, File "/usr/lib/python3.10/runpy.py", line 86, in _run_code exec(code, run_globals) File "/usr/local/lib/python3.10/dist-packages/fmpy/__main__.py", line 4, in main() File "/usr/local/lib/python3.10/dist-packages/fmpy/command_line.py", line 167, in main result = simulate_fmu(args.fmu_filename, File "/usr/local/lib/python3.10/dist-packages/fmpy/simulation.py", line 759, in simulate_fmu result = simulateME(model_description, fmu, start_time, stop_time, solver, step_size, relative_tolerance, start_values, apply_default_start_values, input, output, output_interval, record_events, timeout, step_finished, validate, set_stop_time) File "/usr/local/lib/python3.10/dist-packages/fmpy/simulation.py", line 1076, in simulateME step_event, _ = fmu.completedIntegratorStep() File "/usr/local/lib/python3.10/dist-packages/fmpy/fmi2.py", line 491, in completedIntegratorStep self.fmi2CompletedIntegratorStep(self.component, noSetFMUStatePriorToCurrentPoint, byref(enterEventMode), byref(terminateSimulation)) File "/usr/local/lib/python3.10/dist-packages/fmpy/fmi2.py", line 215, in w raise FMICallException(function=fname, status=res) fmpy.fmi1.FMICallException: fmi2CompletedIntegratorStep failed with status 3 (error).