Environment - simulationEnvironment: startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_latest_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctMixConDischargeSensor.Subsequences.Validation.Alarms -abortSlowSimulation -alarm=480 -s gbode -emit_protected -lv LOG_STATS LOG_SUCCESS | info | The initialization finished successfully without homotopy method. LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.0.0-master/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 954.545457 | | | | ((ala.not2.y)) --> "Warning: airflow is less than 70% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.0.0-master/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2700.000006 | | | | ((ala.not1.y)) --> "Warning: airflow is less than 50% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.0.0-master/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala.truDel7.y)) --> "Warning: the cold-duct or hot-dcut damper is leaking." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.0.0-master/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000001 | | | | ((not ala.truDel6.y)) --> "Warning: airflow sensor should be calibrated." LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.00320779s reading init.xml | | | | | | 0.000284113s reading info.xml | | | | | | 0.000344917s [ 5.7%] pre-initialization | | | | | | 9.0369e-05s [ 1.5%] initialization | | | | | | 6.41e-07s [ 0.0%] steps | | | | | | 1.0765e-05s [ 0.2%] solver (excl. callbacks) | | | | | | 0.00132423s [ 21.9%] creating output-file | | | | | | 0.000221458s [ 3.7%] event-handling | | | | | | 0.000382287s [ 6.3%] overhead | | | | | | 0.00366614s [ 60.7%] simulation | | | | | | 0.00604081s [100.0%] total | | | | | events | | | | | | 7 state events | | | | | | 4 time events | | | | | solver: euler | | | | | | 24176 steps taken | | | | | | 24176 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.