Environment - simulationEnvironment: startTime=0 stopTime=86400 tolerance=1e-06 numberOfIntervals=2500 stepSize=34.56 Regular simulation: ./Buildings_9_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctColdDuctMin.Validation.Controller -abortSlowSimulation -alarm=480 -s cvode -emit_protected -lv LOG_STATS LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((duaDucCon.ala.not8.y)) --> "Warning: the hot-duct damper is leaking." LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((duaDucCon.ala.not5.y)) --> "Warning: the cold-duct damper is leaking." LOG_SUCCESS | info | The initialization finished successfully without homotopy method. LOG_ASSERT | debug | ##CVODE## Desired step to small! LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2160.000000 | | | | ((duaDucCon.gre.greHys.y)) --> "Warning: the sum of minimum flow and heating maximum flow is greater than the cooling maximum flow." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2160.000000 | | | | ((duaDucCon.actAirSet.gre.greHys.y)) --> "Warning: the sum of minimum flow and heating maximum flow is greater than the cooling maximum flow." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 12080.000001 | | | | ((duaDucCon.ala.not7.y)) --> "Warning: hot-duct airflow sensor should be calibrated." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 9.1.2-maint.9.1.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 12080.000001 | | | | ((duaDucCon.ala.not4.y)) --> "Warning: cold-duct airflow sensor should be calibrated." LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.0230978s reading init.xml | | | | | | 0.00191572s reading info.xml | | | | | | 0.00119408s [ 1.5%] pre-initialization | | | | | | 0.000290174s [ 0.4%] initialization | | | | | | 1.9466e-05s [ 0.0%] steps | | | | | | 0.0143409s [ 18.0%] solver (excl. callbacks) | | | | | | 0.00866323s [ 10.9%] creating output-file | | | | | | 0.010484s [ 13.2%] event-handling | | | | | | 0.00113528s [ 1.4%] overhead | | | | | | 0.0433819s [ 54.6%] simulation | | | | | | 0.0795089s [100.0%] total | | | | | events | | | | | | 47 state events | | | | | | 724 time events | | | | | solver: cvode | | | | | | 7911 steps taken | | | | | | 11104 calls of functionODE | | | | | | 769 evaluations of jacobian | | | | | | 99 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.