Environment - simulationEnvironment: startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_11_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Validation.Alarms -abortSlowSimulation -alarm=400 -s cvode -emit_protected -lv LOG_STATS LOG_SUCCESS | info | The initialization finished successfully without homotopy method. LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 954.545457 | | | | ((ala.not2.y)) --> "Warning: airflow is less than 70% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2700.000006 | | | | ((ala.not1.y)) --> "Warning: airflow is less than 50% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala.truDel3.y)) --> "Warning: the damper is leaking." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 11.1.0-maint.11.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000001 | | | | ((ala.not4.y)) --> "Warning: airflow sensor should be calibrated." LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.00385114s reading init.xml | | | | | | 0.000290014s reading info.xml | | | | | | 0.000319158s [ 8.5%] pre-initialization | | | | | | 0.000141846s [ 3.8%] initialization | | | | | | 6.21e-07s [ 0.0%] steps | | | | | | 3.023e-06s [ 0.1%] solver (excl. callbacks) | | | | | | 0.000952947s [ 25.3%] creating output-file | | | | | | 0.00022389s [ 5.9%] event-handling | | | | | | 0.000244745s [ 6.5%] overhead | | | | | | 0.00188538s [ 50.0%] simulation | | | | | | 0.00377161s [100.0%] total | | | | | events | | | | | | 6 state events | | | | | | 4 time events | | | | | solver: euler | | | | | | 12114 steps taken | | | | | | 12114 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.