Environment - simulationEnvironment: startTime=0 stopTime=86400 tolerance=1e-06 numberOfIntervals=523 stepSize=165.201 Regular simulation: ./Buildings_11_Buildings.Fluid.HydronicConfigurations.PassiveNetworks.Examples.DualMixing -abortSlowSimulation -alarm=400 -emit_protected -lv LOG_STATS WARNING: other : Warning: unrecognized command line options -abortSlowSimulation INFO : solver: SimManager: Start initialization ERROR : init : SimManager: Could not initialize system ERROR : init : SimManager: Nonlinear solver 621 stopped at time 0 with error in algloop solver: error solving nonlinear system (iteration limit: 50) ERROR : solver: SimController: Simulation failed using nonlinear solver newton ERROR : solver: SimController: Recovering with nonlinear solver kinsol INFO : solver: SimManager: Start initialization *** Warning: In DualMixing.con: The bypass balancing valve should generate a pressure drop higher than the control valve at design conditions to provide sufficient primary flow. INFO : solver: SimManager: Start simulation at t = 0.000000 INFO : solver: SimManager: Simulation stop time: 86400.000000 INFO : solver: Simulation info from solver: INFO : solver: DASSL: steps taken nst = 2206 INFO : solver: DASSL: residual evaluations nre = 3026 INFO : solver: DASSL: jacobian evaluations nje = 321 INFO : solver: DASSL: root evaluations nrt = 2226 INFO : solver: DASSL: error test failures netf = 98 INFO : solver: DASSL: nonlinear convergence failures ncfn = 7 INFO : solver: DASSL: nonlinear iterations nni = 3026 INFO : solver: DASSL: last evaluation time t = 86523.340824 INFO : solver: DASSL: last step size h = 165.200765 INFO : solver: DASSL: last used order k = 3