Environment - simulationEnvironment: startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_latest_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctMixConDischargeSensor.Subsequences.Validation.Alarms -abortSlowSimulation -alarm=480 -emit_protected -lv LOG_STATS LOG_SUCCESS | info | The initialization finished successfully without homotopy method. assert | info | The following assertion has been violated at time 954.545457 | | | | ala.not2.y assert | info | Warning: airflow is less than 70% of the setpoint. assert | info | The following assertion has been violated at time 2700.000006 | | | | ala.not1.y assert | info | Warning: airflow is less than 50% of the setpoint. assert | info | The following assertion has been violated at time 4350.000000 | | | | not ala.truDel7.y assert | info | Warning: the cold-duct or hot-dcut damper is leaking. assert | info | The following assertion has been violated at time 6225.000001 | | | | not ala.truDel6.y assert | info | Warning: airflow sensor should be calibrated. LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.00363861s reading init.xml | | | | | | 0.000439143s reading info.xml | | | | | | 0.000322605s [ 5.3%] pre-initialization | | | | | | 0.000126838s [ 2.1%] initialization | | | | | | 6.42e-07s [ 0.0%] steps | | | | | | 5.3457e-05s [ 0.9%] solver (excl. callbacks) | | | | | | 0.0013754s [ 22.7%] creating output-file | | | | | | 0.0004247s [ 7.0%] event-handling | | | | | | 0.000412457s [ 6.8%] overhead | | | | | | 0.0033318s [ 55.1%] simulation | | | | | | 0.00604791s [100.0%] total | | | | | events | | | | | | 7 state events | | | | | | 4 time events | | | | | solver: euler | | | | | | 24176 steps taken | | | | | | 24176 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.