Environment - simulationEnvironment: startTime=0 stopTime=86400 tolerance=1e-08 numberOfIntervals=2500 stepSize=34.56 Regular simulation: ./Buildings_12_Buildings.Fluid.HeatPumps.ModularReversible.Examples.Modular_OneRoomRadiator -abortSlowSimulation -alarm=400 -emit_protected -lv LOG_STATS LOG_STDOUT | warning | Internal Numerical Jacobians without coloring are currently not supported by IDA with KLU. Colored numerical Jacobian will be used. LOG_ASSERT | warning | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 12.1.1-maint.12.x/Fluid/HeatPumps/ModularReversible/RefrigerantCycle/BaseClasses/PartialTableData2D.mo:158:3-163:28:writable] | | | | The following assertion has been violated during initialization at time 0.000000 | | | | ((heaPum.refCyc.refCycHeaPumCoo.mEva_flow_nominal <= heaPum.refCyc.refCycHeaPumCoo.mEva_flow_max)) --> "In Modular_OneRoomRadiator.heaPum.refCyc.refCycHeaPumCoo: The nominal evaporator mass flow rate (5.58642 kg/s) is bigger than the | | | | maximal value (3.76014 kg/s) for the table data | | | | when assuming a temperature spread between 3 and 10 K, as in EN 14511." LOG_ASSERT | debug | ##IDA## In function IDAGetNumNonlinSolvIters: The residual function, linear solver setup function, or linear solver solve function had a recoverable failure, but IDACalcIC could not recover. LOG_ASSERT | info | simulation terminated by an assertion at initialization