Environment - simulationEnvironment: startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_10_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.Validation.Alarms -abortSlowSimulation -alarm=400 -emit_protected -lv LOG_STATS LOG_SUCCESS | info | The initialization finished successfully without homotopy method. LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 954.545457 | | | | ((ala1.not2.y)) --> "Warning: airflow is less than 70% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 2700.000006 | | | | ((ala1.not1.y)) --> "Warning: airflow is less than 50% of the setpoint." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala1.truDel7.y)) --> "Warning: the cold-duct or hot-dcut damper is leaking." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala.truDel5.y)) --> "Warning: the hot-duct damper is leaking." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 4350.000000 | | | | ((not ala.truDel3.y)) --> "Warning: the cold-duct damper is leaking." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000001 | | | | ((not ala1.truDel6.y)) --> "Warning: airflow sensor should be calibrated." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000001 | | | | ((not ala.truDel4.y)) --> "Warning: hot-duct airflow sensor should be calibrated." LOG_ASSERT | info | [/home/hudson/saved_omc/libraries/.openmodelica/libraries/Buildings 10.1.1-maint.10.0.x/Controls/OBC/CDL/Utilities/Assert.mo:11:3-14:28:writable] | | | | The following assertion has been violated at time 6225.000001 | | | | ((not ala.truDel2.y)) --> "Warning: cold-duct airflow sensor should be calibrated." LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.00857763s reading init.xml | | | | | | 0.00074102s reading info.xml | | | | | | 0.000706395s [ 11.8%] pre-initialization | | | | | | 0.000166423s [ 2.8%] initialization | | | | | | 1.062e-06s [ 0.0%] steps | | | | | | 2.7826e-05s [ 0.5%] solver (excl. callbacks) | | | | | | 0.00156182s [ 26.1%] creating output-file | | | | | | 0.000426184s [ 7.1%] event-handling | | | | | | 0.000271846s [ 4.5%] overhead | | | | | | 0.00281936s [ 47.1%] simulation | | | | | | 0.00598091s [100.0%] total | | | | | events | | | | | | 7 state events | | | | | | 4 time events | | | | | solver: euler | | | | | | 12126 steps taken | | | | | | 12126 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.