startTime=0 stopTime=7200 tolerance=1e-06 numberOfIntervals=2500 stepSize=2.88 Regular simulation: ./Buildings_latest_Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.DualDuctSnapActing.Subsequences.Validation.Alarms -abortSlowSimulation -alarm=480 -lv LOG_STATS LOG_SUCCESS | info | The initialization finished successfully without homotopy method. assert | info | The following assertion has been violated at time 954.545457 | | | | ala1.not2.y assert | info | Warning: airflow is less than 70% of the setpoint. assert | info | The following assertion has been violated at time 2700.000006 | | | | ala1.not1.y assert | info | Warning: airflow is less than 50% of the setpoint. assert | info | The following assertion has been violated at time 3750.000000 | | | | ala1.not11.y assert | info | Warning: the cold-duct or hot-dcut damper is leaking. assert | info | The following assertion has been violated at time 3750.000000 | | | | ala.not8.y assert | info | Warning: the hot-duct damper is leaking. assert | info | The following assertion has been violated at time 3750.000000 | | | | ala.not5.y assert | info | Warning: the cold-duct damper is leaking. assert | info | The following assertion has been violated at time 6225.000001 | | | | ala1.not9.y assert | info | Warning: airflow sensor should be calibrated. assert | info | The following assertion has been violated at time 6225.000001 | | | | ala.not7.y assert | info | Warning: hot-duct airflow sensor should be calibrated. assert | info | The following assertion has been violated at time 6225.000001 | | | | ala.not4.y assert | info | Warning: cold-duct airflow sensor should be calibrated. LOG_STATS | info | ### STATISTICS ### | | | | | timer | | | | | | 0.0053919s reading init.xml | | | | | | 0.000637356s reading info.xml | | | | | | 8.1943e-05s [ 1.4%] pre-initialization | | | | | | 0.000100578s [ 1.7%] initialization | | | | | | 8.01e-07s [ 0.0%] steps | | | | | | 1.2814e-05s [ 0.2%] solver (excl. callbacks) | | | | | | 0s [ 0.0%] creating output-file | | | | | | 0.000649021s [ 10.8%] event-handling | | | | | | 0.000394356s [ 6.6%] overhead | | | | | | 0.00477279s [ 79.4%] simulation | | | | | | 0.00601231s [100.0%] total | | | | | events | | | | | | 7 state events | | | | | | 3 time events | | | | | solver: euler | | | | | | 20970 steps taken | | | | | | 20970 calls of functionODE | | | | | | 0 evaluations of jacobian | | | | | | 0 error test failures | | | | | | 0 convergence test failures | | | | | | 0s time of jacobian evaluation LOG_SUCCESS | info | The simulation finished successfully.